Operating voltage DC 13.5…35 V
Measuring range, temperature 0…50 °C, -35…35 °C, -40…70 °C
Measurement range humidity 0…100 % r.h.
Measurement accuracy Humidity at 0…100 % r.h. and 23 °C: ±2 % r.h., Temperature, at 15…35 °C: ±0.6 K, Temperature, at 40…70 °C: ±0.8 K
Time constant Humidity: <20 s, Temperature in with 2 m/s moved air: <3.5 min
Immersion length 90…206 mm
Connection, electrical Round connector
Type of fixing Flange
Signal output temperature DC 4…20 mA
Signal output humidity DC 4…20 mA
Degree of protection IP65
Dimensions (W x H x D) 80 x 117 x 39 mm